SM6-24 DM1A Mot 220Vac, ESERGY P3U20, 1 CTB cubicle
Rp. 0,-
|
Main |
||
|
range of product |
SM6-24 |
|
|
technology type |
Air insulated switchgear |
|
|
device short name |
DM1A |
|
|
product or component type |
Cubicle |
|
|
isolation |
Single isolation |
|
|
internal arc protection |
12.5 kA 1 s |
|
|
Rated frequency (fr) |
50 Hz |
|
|
Rated lightning impulse withstand voltage (Up) |
125 kV peak |
|
|
Rated voltage (Ur) |
24 kV |
|
|
Rated normal current (Ir) |
630 A |
|
|
rated short-time withstand current (Ik) |
16 kA rms 1 s |
|
|
Rated short-duration power-frequency withstand voltage (Ud) |
28 kV rms 50 Hz for 1 min |
|
|
standards |
IEC 62271-200 |
|
|
Complementary |
||
|
Primary current transformer |
......... A |
|
|
pole distance |
250 mm phase to phase |
|
|
creepage distance |
470 mm input/output |
|
|
inter contact distance |
380 mm |
|
|
bus rated current |
630 A |
|
|
type of operator |
CS |
|
|
control circuit voltage (Uc) |
220 V AC opening coil |
|
|
mechanical interlocking |
Type 50 |
|
|
accessory / separate part destination |
T20 HMI |
|
|
additional device type |
Protection relay Easergy P3 |
|
|
protection type |
Circuit breaker |
|
|
CB name |
SF1 type 1 |
|
|
CB installation |
Disconnectable |
|
|
CB operating position |
Left-hand side (B1) |
|
|
CB poles description |
3P |
|
|
CB rated switching sequence |
O - 3 min - CO - 3 min - CO |
|
|
operating time |
< 50 ms opening |
|
|
CB charging time |
15 s |
|
|
CB rated interrupted current |
50 A C2 cable charging: |
|
|
net weight |
400 kg |
|
|
width |
750 mm |
|
|
depth |
1220 mm |
|
|
|
|
|
|
Environment |
||
|
ambient air temperature for operation |
-5…40 °C |
|
|
ambient air temperature for storage |
-40…70 °C |
|
|
IP degree of protection |
IP3x |
|
|
vibration resistance |
0.5 gn horizontal |
|
|
operating altitude |
<= 1000 m |
|
|
|
|
|
|
Offer Sustainability |
||
|
EU RoHS Directive |
Not applicable, out of EU RoHS legal scope |
|
|
Contractual warranty |
||
|
Warranty |
12 months |
SUmber : DataSheet