MAIN

Range of product SM6-24

Technology typeAir insulated switchgear

Device short name QM 500

Product or component type Fuse-Switch

Internal arc protection 12.5 kA 1 s

Internal arc classification A-FL downward exhaust gas

Rated frequency (fr) 50 Hz

Rated lightning impulse with stand voltage (Up)125 kV peak

Rated voltage (Ur) 24 kVRated normal current (Ir) 630 A

Rated short-time with stand current (Ik) 16 kA 1 s

Rated short-duration power-frequency with stand voltage (Ud) 28 kV 50 Hz for 1 min

 

Complementary

Cable connection 1 x 95 mm² per phase (bottom)

Bus rated current 630 A

Type of operator CI1 manual

Control circuit voltage(uC) 220V AC Opening Coil

Fuse type 6,3...125A

Number of contact 2

Contact type and composition 1 NO + 1 NC

Counting device type Operating counter optional

Device composition thermal sensor TH110 (integrated)

Net weight 130 kg

Width 500 mm

Depth 950 mm

 

Environment

Standards IEC 62271-200

Ambient air temperature for operation -5…40 °C

Ambient air temperature for storage -40…70 °C

IP degree of protection IP3x

Vibration resistance 0.5 gn horizontal class 20.4 gn vertical class 2

Operating altitude <= 1000 m

 

Contractual warranty