Range of product SM6-24

Technology type Air insulated switchgear

short name IM 500

Product or component type Switch

Internal arc protection 12.5 kA 1 s

Internal arc classification A-FL downward exhaust gas

Rated frequency (fr) 50 Hz

Rated lightning impulse with stand voltage (Up)125 kV peak

Rated voltage (Ur) 24 kV

Rated normal current (Ir) 630 A

Rated short-time withstand current (Ik) 16 kA 1 s

Rated short-duration power-frequency with stand voltage (Ud)28 kV 50 Hz for 1 min

 

Complementary

Cable connection 1 x 240 mm² per phase (bottom)

Bus rated current 630 A

Type of operator CIT manual

Counting device type Operating counter optional

Device composition thermal sensor TH110 (integrated)

Net weight 130 kg

Height 1700 mm

Width 500 mm

Depth 950 mm

 

Environment

Standards IEC 62271-200

Ambient air temperature for operation -5…40 °C

Ambient air temperature for storage -40…70 °C

IP degree of protection IP22

Vibration resistance 0.5 gn horizontal class 2

0.4 gn vertical class 2

Operating altitude <= 1000 m

 