SM6-IM Manual 24KV
MAIN
Range of product SM6-24
Technology type Air insulated switchgear
short name IM 500
Product or component type Switch
Internal arc protection 12.5 kA 1 s
Internal arc classification A-FL downward exhaust gas
Rated frequency (fr) 50 Hz
Rated lightning impulse with stand voltage (Up)125 kV peak
Rated voltage (Ur) 24 kV
Rated normal current (Ir) 630 A
Rated short-time withstand current (Ik) 16 kA 1 s
Rated short-duration power-frequency with stand voltage (Ud)28 kV 50 Hz for 1 min
Complementary
Cable connection 1 x 240 mm² per phase (bottom)
Bus rated current 630 A
Type of operator CIT manual
Counting device type Operating counter optional
Device composition thermal sensor TH110 (integrated)
Net weight 130 kg
Height 1700 mm
Width 500 mm
Depth 950 mm
Environment
Standards IEC 62271-200
Ambient air temperature for operation -5…40 °C
Ambient air temperature for storage -40…70 °C
IP degree of protection IP22
Vibration resistance 0.5 gn horizontal class 2
0.4 gn vertical class 2
Operating altitude <= 1000 m
Contractual warranty
Warranty 12 months